Special line of FGR-V series heat exchangers for Viessmann boilers
HEAT UTILIZERS OF THE FGR-V SERIES Viessmann boilers
FGR-V is our company’s own development with patented technology.
All FGR models comply with TU U25.3-43696619-001:2023 HEAT UTILIZERS OF THE ” FGR ” SERIES. Specifications.
This is a special line of exhaust gas/water heat exchangers for the use of condensation heat, which are made of corrosion-resistant materials and are designed to work with boilers manufactured by Viessmann .
FGR-V waste gas/water heat exchangers for operation on gas and liquid boiler fuel (EL)
Compatible Viessmann models
– Vitoplex 100 with a capacity of 575-1750 kW;
– Vitoplex 200 with a capacity of 90-560 kW;
– Vitoplex 300 with a capacity of 80-1750 kW;
– Vitorond 200 with a capacity of 125-1080 kW;
– Vitomax 100-LW with a capacity of 650–6000 kW;
– Vitomax 200 with a capacity of 2100-6000 kW;
– Vitomax 300 with a capacity of 1860–5900 kW;
ADVANTAGES AND FEATURES OF THE DESIGN
– For heating installations with a permissible supply temperature of up to 110 °C;
– High operational reliability and long service life thanks to the use of corrosion-resistant materials, all FGR-V are manufactured with a condensing surface based on E – Fin – a tube with a high fin density .
– Compact design that saves space, the heat exchanger is installed directly behind the water heating boiler, there is an option to install the explosion valve of the boiler on the project site;
– Simplicity of hydraulic tying: adjustment of volume flow through FGR-V, it is possible to pass the entire volume flow, which allows optimal use of condensation heat;
– E – Fin heat exchange surfaces and several water passages in the opposite direction of gas flow provide highly efficient heat exchange and acceleration of the condensation process;
– It is possible to supply condensate neutralization devices coordinated with FGR-V gas/water heat exchangers, which are mounted directly on the FGR-V frame without taking up additional space;
– All models of heat exchangers of the FGR-V series are suitable for operation with gas and short-term operation with light boiler fuel EL with a dual-fuel burner ;
– The FGR-V stainless steel 1.4539 version is available – for continuous operation on light EL boiler fuel using condensation heat.
KIT
The main one
Frame construction of the heat exchanger.
Thermal insulation.
Bed with height adjustment.
Counter flanges and collectors of the connection of the gas main.
Couplings for connecting ¬gas temperature sensors.
Additional
On-board boiler relief valve (for installation of FGR-V in the design space of the location of the boiler relief valve).
Condensate neutralization station.
Irrigation system of flue gases with condensate (additional increase in efficiency of the heat exchanger by 3-10%)
Special executions are possible on request.
TECHNICAL DATA FGR-V
FGR-V for Vitoplex and Vitorond (up to 560 kW)
| Characteristic | Unit | Indexes | |||
| Nominal thermal power of the boiler
Vitoplex 300 (TX3 type) Vitoplex 200 (3X2 type) Vitoplex 200 |
kW |
80-105 90-120 125 |
130-170 150-200 160-195 |
225-285 270-350 230-320 |
345-460 440-560 380-560 |
| Nominal heat capacity of the heat exchanger (gas)* | from kW to kW |
7,7 11,9 |
11,8 19,0 |
21,3 33,3 |
30,3 48,9 |
| Nominal heat capacity of the heat exchanger (liquid fuel EL)* | from kW to kW |
5,2 8,1 |
8,2 13,0 |
14,6 22,7 |
20,8 33,5 |
| Permissible excess working pressure | bar | 4 | 4 | 4 | 6 |
| Allowed temperature of the falling line | °С | 110 | 110 | 110 | 110 |
| Resistance of the exhaust gas side | mbar | 0,65 | 0,85 | 1,0 | 10,5 |
| Mass consumption of waste gases | from kg/h to kg/h |
136 213 |
213 341 |
383 596 |
546 954 |
| Mass and dimensional indicators
Total length |
mm |
667 |
781 |
859 |
995 |
| The volume of the coolant | l | 70 | 97 | 134 | 181 |
| Gas volume | m3 | 0,055 | 0,096 | 0,133 | 0,223 |
| Connection of supply and return lines | DN | 40 | 50 | 50 | 65 |
| Condensate drain | R | 1⁄2 | 1⁄2 | 1⁄2 | 1⁄2 |
| Combustion product removal system pipe to the boiler | ∅ mm | 180 | 200 | 200 | 200 |
| Combustion product removal system pipe to the exhaust system | ∅ mm | 150 | 200 | 200 | 250 |
FGR-V for Vitoplex (575 – 1750 kW)
| Characteristic | Unit | Indexes | |||||||
| Nominal thermal power of the boiler | kW | 575 | 720 | 895 | 1120 | 1400 | 1750 | ||
| Nominal heat capacity of the heat exchanger (gas)* | kW | 55 | 68 | 85 | 106 | 133 | 166 | ||
| Nominal heat capacity of the heat exchanger (liquid fuel EL)* | kW | 37 | 47 | 58 | 73 | 91 | 114 | ||
| Permissible excess working pressure | bar | 6 | 6 | 6 | 6 | 6 | 6 | ||
| Allowed temperature of the falling line | °С | 110 | 110 | 110 | 110 | 110 | 110 | ||
| Resistance of the exhaust gas side | mbar | 0,8 | 1,3 | 0,8 | 1,3 | 1,3 | 2,1 | ||
| Mass consumption of waste gases | kg/h | 980 | 1225 | 1525 | 1910 | 2390 | 2980 | ||
| Mass and dimensional indicators
Total length |
mm |
824 |
964 |
1092 |
|||||
| The volume of the coolant | l | 135 | 275 | 380 | |||||
| Gas volume | m3 | 0,193 | 0,389 | 0,683 | |||||
| Connection of supply and return lines | DN | 80 | 100 | 125 | |||||
| Condensate drain | R | 1⁄2 | 1⁄2 | 1⁄2 | |||||
| Flue gas duct connection pipe | DN ∅ mm | 250 | 300 | 400 | |||||
FGR-V for Vitoplex (630 – 1080 kW)
| Characteristic | Unit | Indexes | |||||
| Nominal thermal power of the boiler | kW | 630 | 700 | 780 | 860 | 950 | 1080 |
| Nominal heat capacity of the heat exchanger (gas)* | kW | 59 | 66 | 74 | 81 | 90 | 102 |
| Nominal heat capacity of the heat exchanger (liquid fuel EL)* | kW | 41 | 45 | 50 | 55 | 61 | 70 |
| Permissible excess working pressure | bar | 6 | 6 | 6 | 6 | 6 | 6 |
| Allowed temperature of the falling line | °С | 110 | 110 | 110 | 110 | 110 | 110 |
| Resistance of the exhaust gas side | mbar | 1,0 | 1,25 | 0,65 | 0,75 | 0,95 | 1,2 |
| Mass consumption of waste gases | kg/h | 1074 | 1193 | 1329 | 1466 | 1620 | 1841 |
| Mass and dimensional indicators
Total length |
mm |
824 |
964 |
||||
| The volume of the coolant | l | 135 | 275 | ||||
| Gas volume | m3 | 0,193 | 0,389 | ||||
| Connection of supply and return lines | DN | 80 | 100 | ||||
| Condensate drain | R | 1⁄2 | 1⁄2 | ||||
| Flue gas duct connection pipe | DN ∅ mm | 250 | 300 | ||||
FGR-V for Vitoplex and Vitorond (1860 – 6600 kW)
| Characteristic | Unit | Indexes | ||||||
| Nominal thermal power of the boiler
Vitomax 200 Vitomax 300 |
kW |
2100 1860 |
2600 2300 |
3200 2900 |
3900 3500 |
4500 4100 |
5300 4700 |
6600 5900 |
| Nominal heat capacity of the heat exchanger (gas)* | from kW to kW |
177 200 |
219 248 |
276 305 |
333 371 |
390 428 |
447 504 |
561 628 |
| Nominal heat capacity of the heat exchanger (liquid fuel EL)* | from kW to kW |
121 137 |
150 170 |
189 209 |
228 254 |
267 293 |
306 345 |
384 430 |
| Permissible excess working pressure | bar | 10 | 10 | 10 | 10 | 10 | 10 | 10 |
| Allowed temperature of the falling line | °С | 110 | 110 | 110 | 110 | 110 | 110 | 110 |
| Resistance of the exhaust gas side | mbar | 1,3 | 1,9 | 1,7 | 2,5 | 2,3 | 3,2 | 3,8 |
| Mass consumption of waste gases | from kg/h to kg/h |
3070 3510 |
3795 4340 |
4785 5340 |
5775 6510 |
6765 7510 |
7755 8850 |
9730 11000 |
| Mass and dimensional indicators
Total length |
mm |
1320 |
1450 |
1550 |
1650 |
|||
| The volume of the coolant | l | 430 | 500 | 630 | 750 | |||
| Gas volume | m3 | 0,661 | 1,040 | 1,402 | 1,876 | |||
| Connection of supply and return lines | DN | 150 | 200 | 200 | 250 | |||
| Condensate drain | R | 1 1⁄4 | 1 1⁄4 | 1 1⁄4 | 1 1⁄4 | |||
| Flue gas duct connection pipe | DN ∅ mm | 500 | 600 | 700 | 800 | |||
IMPORTANTLY
– The burner must overcome the total resistance on the side of the flue gases of the water heating boiler, FGR-V and gas duct.
– When using FGR-V, the excess working pressure of the heating installation should not exceed 4 bar.
– The gas nozzles of the water heating boiler and the waste gas/water heat exchanger are aligned with adjusting screws so that they are located at the same height, after which they must be connected by a connecting sleeve.
– The thermal power data of the exhaust gas heat exchanger/FGR-V driver are given for an exhaust gas inlet temperature of 200 °C and an inlet coolant temperature in the heat exchanger of 40 °C.
FGR-V E SERIES HEAT UTILIZERS
This is a special line of waste gas/water heat exchangers (economizers) for using waste gas heat and designed to work with Viessmann boilers .
FGR-V E waste gas/water heat exchangers ( economizers) for operation on gas and liquid boiler fuel (EL)
Compatible Viessmann models
– Vitomax 100-LW with a capacity of 650–6000 kW;
– Vitomax 200-LW with a capacity of 2100-6000 kW;
ADVANTAGES AND FEATURES OF THE DESIGN
– All models of heat exchangers (economizers) of the FGR- V E series , suitable for short-term operation (up to 25%) in condensation mode ;
KIT
The main one
Frame construction of the heat exchanger.
Thermal insulation.
Bed with height adjustment.
Counter flanges and collectors of the connection of the gas main.
Couplings for connecting ¬gas temperature sensors.
Additional
On-board boiler blow-off valve (for installation of FGR- V E on the design space of the location of the boiler blow-off valve).
Special executions are possible on request.
TECHNICAL DATA FGR-VE
FGR-VE for Vitomax 100-LW (2300 – 6000 kW)
| Characteristic | Unit | Indexes | |||||
| Nominal thermal power of the boiler | kW | 2300 | 2900 | 3500 | 4200 | 5000 | 6000 |
| Nominal heat capacity of the heat exchanger (gas)* | kW | 110 | 140 | 171 | 207 | 240 | 296 |
| Nominal heat capacity of the heat exchanger (liquid fuel EL)* | kW | 97 | 124 | 151 | 184 | 213 | 262 |
| Permissible excess working pressure | bar | 16 | |||||
| Permissible supply line temperature | °С | 120 | |||||
| Permissible return temperature | °С | 65 | |||||
| Water circuit resistance | mbar | 174 | 174 | 174 | 175 | 175 | 176 |
| Exhaust gas resistance, (gas) | Pa | 123 | 127 | 127 | 196 | 156 | 217 |
| Exhaust gas resistance, (liquid fuel EL) | Pa | 110 | 114 | 113 | 175 | 140 | 194 |
| Exhaust gas mass flow rate (gas) | kg/h | 1,5225 x combustion chamber capacity kW | |||||
| Exhaust gas mass flow rate (liquid fuel EL) | kg/h | 1,5 x combustion chamber capacity kW | |||||
| Mass and dimensional indicators
Total length |
mm |
1586 |
1586 |
1586 |
1666 |
1586 |
1486 |
| The volume of the coolant | m3 | 0,2 | 0,23 | 0,29 | 0,34 | 0,34 | 0,42 |
| Gas volume | m3 | 0,27 | 0,34 | 0,41 | 0,4 | 0,53 | 0,54 |
| Connection of supply and return lines | DN/PN | 150/40 | 150/40 | 200/25 | 200/25 | 200/25 | 200/25 |
| Draining the water circuit | G | 1⁄2 | |||||
| Emptying the gas circuit | R | 1⁄2 | |||||
| Measuring sleeves | R | 1⁄2 | |||||
| Exhaust system pipe (external) | ∅ mm | 410 | 460 | 510 | 560 | 610 | 660 |
| Exhaust system pipe (internal) | ∅ mm | 400 | 450 | 500 | 550 | 600 | 650 |
FGR-VE for Vitomax 200-LW (2300 – 6000 kW)
| Characteristic | Unit | Indexes | ||||
| Nominal thermal power of the boiler | kW | 2300 | 2900 | 3500 | 4500 | 6000 |
| Nominal heat capacity of the heat exchanger (gas)* | kW | 89 | 103 | 139 | 167 | 241 |
| Nominal heat capacity of the heat exchanger (liquid fuel EL)* | kW | 81 | 95 | 127 | 153 | 220 |
| Permissible excess working pressure | bar | 16 | ||||
| Permissible supply line temperature | °С | 120 | ||||
| Permissible return temperature | °С | 65 | ||||
| Water circuit resistance | mbar | 174 | 174 | 174 | 175 | 176 |
| Exhaust gas resistance, (gas) | Paа | 118 | 101 | 122 | 190 | 209 |
| Exhaust gas resistance, (liquid fuel EL) | Pa | 106 | 91 | 110 | 171 | 188 |
| Exhaust gas mass flow rate (gas) | kg/h | 1,5225 x combustion chamber capacity kW | ||||
| Exhaust gas mass flow rate (liquid fuel EL) | kg/h | 1,5 x combustion chamber capacity kW | ||||
| Mass and dimensional indicators
Total length |
mm |
1586 |
1486 |
1586 |
1586 |
1666 |
| The volume of the coolant | m3 | 0,2 | 0,19 | 0,29 | 0,29 | 0,42 |
| Gas volume | m3 | 0,27 | 0,35 | 0,41 | 0,4 | 0,54 |
| Connection of supply and return lines | DN/PN | 150/40 | 150/40 | 200/25 | 200/25 | 200/25 |
| Draining the water circuit | G | 1⁄2 | ||||
| Emptying the gas circuit | R | 1⁄2 | ||||
| Measuring sleeves | R | 1⁄2 | ||||
| Exhaust system pipe (external) | ∅ mm | 410 | 460 | 510 | 560 | 660 |
| Exhaust system pipe (internal) | ∅ mm | 400 | 450 | 500 | 550 | 650 |
IMPORTANTLY
– The burner must overcome the total resistance on the side of the flue gases of the water heating boiler, FGR-V and gas duct.
– When using FGR-V, the excess working pressure of the heating installation should not exceed 4 bar.
– The gas nozzles of the water heating boiler and the waste gas/water heat exchanger are aligned with adjusting screws so that they are located at the same height, after which they must be connected by a connecting sleeve.
– The heat output of the FGR-V heat exchanger at a flue gas temperature of 182 °C (HEL liquid fuel) or 188 °C (gas) and a system temperature of 90/70 °C.
– A long-term (more than 25% of the operating time) temperature drop below the dew point of flue gases is unacceptable.